Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
K3 | 418D | K3 | A calibration constant generated during a flowing (3rd point) density calibration. | R/W | Float | 8 |
flow_pres_factor | 418E | Flow factr | Pressure compensation factor applied to flow rate (% change per PSI). | R/W | Float | 8 |
dens_pres_factor | 418F | Dens factr | Pressure compensation factor applied to density (g/Cucm change per PSI). | R/W | Float | 8 |
zero_pres_factor | 4189 | Flowcal pressure | Pressure at which flow calibration was performed. | R/W | Float | 8 |
ma4_pressure | 418A | 4 mA pressure | Used by the Analog Input, this is the pressure (from external pressure transmitter) which is indicated by the 4 mA signal. | R/W | Float | 8 |
ma20_pressure | 418B | 20 mA pressure | Used by the Analog Input, this is the pressure (from external pressure transmitter) which is indicated by the 20 mA signal. | R/W | Float | 8 |
mass_flow_digital_units | 4007 | Еди-ца расхода | Единицы измерения переменной полевого устройства - ед.изм., которые должна отображаться с 'Числовым значением', 'Минимальным диапазоном', 'Значение верхнего предела диапазона', 'Значение нижнего предела диапазона', 'Нижний предел сенсора' и 'Верхний предел сенсора' | R/W | Enum | 32 |
mass_flow_digital_value | 4008 | Масс. расх. | R | Float | 2 | |
mass_flow_digital_cutoff | 400A | Выкл. масс. расх. | The mass flow rate below which the frequency/pulse output indicates zero flow, and below which totalizers stop counting. | R/W | Float | 8 |
mass_flow_analog_value | 400B | Анал. зн. масс. расх. | R/W | Float | 66 | |
Name | ID | Label | Description | Type | Access | Class |