Loading…
Name ID Label Description Type Access Class
temp_analog_value_1 419C Temp anlog valu R/W Float 66
temp_additional_analog_damping_1 419D Added damp Analog Output Added Damping Value- Damping time constant applied the Analog Output. The units of this variable are always in seconds. R/W Float 32
temp_percent_range_1 419E Temp % rnge Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
temp_upper_range_value_1 419F Temp URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
temp_lower_range_value_1 41A0 Temp LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
temp_upper_sensor_limit 402C Temp URL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
temp_digital_damping 402D Temp damp Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. R/W Float 32
temp_lower_sensor_limit 402E Temp LRL Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 8
temp_minimum_span 402F Temp min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 8
mtot_digital_units 4032 Mass totl unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R Enum 32
Name ID Label Description Type Access Class