Name ID Label Description Type Access Class
sp_volume_total_text 40A2 Vol totl text A 1 to 4 character description of a special unit of volume, which is based on the special unit of flow to represent total. R/W ASCII 2048
fixfreq 40A3 Fixed freq A value (in Hertz) that will be indicated on the frequency output for the purpose of a loop test. R/W Float 4096
totctl 40A4 Totlizer cntrl Allows the user to Reset, Stop, or Start all totalizers. NOTE - Inventory totals are NOT reset. R/W Enum 4096
dencal 40A5 Dens calib factr 14 characters describing the sensitivity of the sensor to density. R/W ASCII 32
max_zero 40A6 Zero time The number of readings collected from the sensor during an Auto Zero operation. R/W Unsigned 4
conv_lim 40A7 Converg. limit A unitless number that allows the user to reject the Auto Zero operation if the standard deviation is greater than 10 times the programmed convergence limit. A convergence limit of zero disables this feature. R/W Float 16
pulse_width 40A8 Max pulse width For the RFT9739, a programmable time period, in seconds, that defines the crossover frequency for the frequency output, where Crossover freq. = 1 / (2 x Pulse width). Below the crossover, the output has a constant ON state, and an OFF state that varies with frequency. R/W Float 512
control 40A9 Control output An output that produces 0 V ON and 15 OFF digital levels. The control output can represent faults, zero in progress, flow direction, event 1 or event 2. R/W Enum 1024
tempcal 40AA Temp cal factr A 14-character factor that describes the slope and offset of the linear output representing flow tube temperature. R/W ASCII 32
rt_zero 40AB Zero A value, in microseconds, representing the phase shift between velocity signals from the sensor when measuring zero flow. R Float 2
Name ID Label Description Type Access Class