名称 ID 标签 描述 类型 访问 分类
rt_sigma 40CD Standard Deviation A unitless value which characterizes the amount of deviation between readings during an Auto Zero operation. 浮点 10
fault_index 40CE Output Type 读/写 索引 4096
LMV_fault_timeout 40D0 故障超时 This parameter defines the number of seconds for which all outputs will hold their last measured value prior to going to the configured fault state. The default is zero seconds. 读/写 无符号 12
ao_1_fault_code 40D3 故障动作 下限:指示流量的毫安输出指向该组态限值。上限:毫安输出指向该组态限值。内部调零:流量输出值指示零流量。 读/写 枚举 12
ao_1_fault_level 40D5 Fault Level (Direct) This parameter allows you to select the lower or upper mA output level that will indicate a fault condition. For a 12-20 mA output (Direct), the range is 11.5 to 11.8 mA for downscale or 20.5 to 22.0 for upscale. For a 4-20 mA output (Level-Shifted), the range is 3.0 to 3.6 mA for downscale or 21.0 to 24.0 for upscale. 读/写 浮点 66
ao_1_fault_level_4_20 40D7 故障等级(适配器势垒) This parameter allows you to select the lower or upper mA output level that will indicate a fault condition. For a 12-20 mA output (Direct), the range is 11.5 to 11.8 mA for downscale or 20.5 to 22.0 for upscale. For a 4-20 mA output (Level-Shifted), the range is 3.0 to 3.6 mA for downscale or 21.0 to 24.0 for upscale. 读/写 浮点 66
dig_comm_fault_code 40D9 数字通讯故障动作 This fault setting applies to Modbus on RS485 and the display. Downscale: Hold process variables at values that are less than the Lower Sensor Limits and stop totalizing. Upscale: Hold process variables at values that are greater than the Upper Sensor Limits and stop totalizing. Not-a-Number: Set all process variables to IEEE NaN. IntZero-All 0: Set all process variables to 0. IntZero-Flow 0: Set flow rate to 0. None: Process variables displayed as measured (NOTE: Use alternative method to detect fault conditions when NONE is selected) 读/写 枚举 12
density_for_cal 40DE 读/写 浮点 4096
point_code 40DF 读/写 无符号 4096
densityfd_for_cal 40E0 读/写 浮点 4096