Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
temp_digital_units | 4022 | Temperature Unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. | R/W | Enum | 32 |
temp_digital_value | 4023 | Temperature | R | Float | 10 | |
temp_analog_value | 4024 | Temperature mA Value | R/W | Float | 66 | |
temp_analog_4_20_value | 4025 | Temperature mA Value | R/W | Float | 66 | |
temp_analog_upper_limit | 4026 | mA Output Upper Limit | Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions | R | Float | 64 |
temp_analog_lower_limit | 4027 | mA Output Lower Limit | mA output Lower Endpoint Value- Defines the lower endpoint, of the respective mA output, for normal operating conditions. | R | Float | 64 |
temp_additional_analog_damping | 4028 | Added Damping | mA Output Added Damping Value- Damping time constant applied the mA output. The units of this variable are always in seconds. | R/W | Float | 32 |
temp_percent_range | 4029 | Temperature Percent Range | Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. | R | Float | 34 |
temp_upper_range_value | 402A | Temperature Upper Range Value | This is the 20mA point. Defines the operational endpoint from which the Analog Value and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines the point above which all high alarms (both analog and digital) for the assigned process variable are activated. | R/W | Float | 32 |
temp_lower_range_value | 402B | Temperature Lower Range Value | This is the 12 mA point (Direct) or the 4 mA point (Level-Shifted). Defines the operational endpoint from which the Analog Value and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines the point below which all low alarms (both analog and digital) for the assigned process variable are activated. | R/W | Float | 32 |
Name | ID | Label | Description | Type | Access | Class |