Name ID Label Description Type Access Class
pres_digital_value 405D External Pressure Pressure value from an external device. R Float 10
pres_analog_value 405E mA Output (Direct) R/W Float 66
pres_analog_4_20_value 405F mA Output (Direct) R/W Float 66
pres_analog_upper_limit 4060 mA Output Upper Limit Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions R Float 64
pres_analog_lower_limit 4061 mA Output Lower Limit mA output Lower Endpoint Value- Defines the lower endpoint, of the respective mA output, for normal operating conditions. R Float 64
pres_percent_range 4062 Percent Range Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
pres_upper_range_value 4063 Upper Range Value This is the 20mA point. Defines the operational endpoint from which the Analog Value and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines the point above which all high alarms (both analog and digital) for the assigned process variable are activated. R/W Float 32
pres_lower_range_value 4064 Lower Range Value This is the 12 mA point (Direct) or the 4 mA point (Level-Shifted). Defines the operational endpoint from which the Analog Value and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines the point below which all low alarms (both analog and digital) for the assigned process variable are activated. R/W Float 32
pres_upper_sensor_limit 4065 Upper Sensor Limit Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
pres_lower_sensor_limit 4066 Lower Sensor Limit Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 8
Name ID Label Description Type Access Class