Name ID Label Description Type Access Class
dens_analog_4_20_value 403B Density mA Value R/W Float 66
dens_analog_upper_limit 403C mA Output Upper Limit Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions R Float 64
dens_analog_lower_limit 403D mA Output Lower Limit mA output Lower Endpoint Value- Defines the lower endpoint, of the respective mA output, for normal operating conditions. R Float 64
dens_additional_analog_damping 403E Added Damping mA Output Added Damping Value- Damping time constant applied the mA output. The units of this variable are always in seconds. R/W Float 32
dens_percent_range 403F Density Percent Range Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
dens_upper_range_value 4040 Density Upper Range Value This is the 20mA point. Defines the operational endpoint from which the Analog Value and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines the point above which all high alarms (both analog and digital) for the assigned process variable are activated. R/W Float 32
dens_lower_range_value 4041 Density Lower Range Value This is the 12 mA point (Direct) or the 4 mA point (Level-Shifted). Defines the operational endpoint from which the Analog Value and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines the point below which all low alarms (both analog and digital) for the assigned process variable are activated. R/W Float 32
dens_upper_sensor_limit 4038 Density Upper Sensor Limit Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
dens_digital_damping 4042 Density Damping Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective mA output. The units of this variable are always in seconds. R/W Float 32
dens_lower_sensor_limit 4043 Density Lower Sensor Limit Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 8
Name ID Label Description Type Access Class