Loading…
Name ID Label Description Type Access Class
statusinfo_10 406A Signal Too Low Signal Too Low - Level signal amplitude is insufficient; choose lower Dielectric range, increase Turbulence or Foam settings, consult Factory if problem persists. R Enum 2050
statusinfo_11 406B Info 0800 R Enum 2050
statusinfo_12 406C IPC Bus IPC Bus - Internal communications error; consult Factory. R Enum 2050
statusinfo_13 406D IPC Checksum IPC Checksum - Internal communications error; consult Factory. R Enum 2050
statusinfo_14 406E IPC Length IPC Length - Internal communications error; consult Factory. R Enum 2050
statusinfo_15 406F IPC Ack IPC Ack - Internal communications error; consult Factory. R Enum 2050
TargetsMode 4070 Mode Review all Targets detected by the transmitter including false targets (targets other than Level). Ensure that the proper Level target is shown then run Target Rejection routine. If reported Level is close to actual and the quality number is > 20, it is probably correct. Targets can be viewed in Level or Distance mode. R/W Enum 2048
TargRejStatus 400F Status The Target Rejection routine detects, stores, and cancels false targets to ensure detection of the proper level signal. The No False Target Rejection warning message will be displayed if this algorithm is not enabled. Do not proceed with False Target Rejection procedure until confirming Level and Quality values in Targets menu. False Target Rejection should be run with vessel at or near empty when all targets are exposed; re-run this routine if initial calibration is done with significant liquid in vessel. The false target profile will be disabled and this routine should be re-run if antenna or tank parameters are modified or when launcher is repositioned. R Enum 2050
TargRejStatusType 40AC Target Rej Type R Enum 2048
TargRejAction_requested 40AD W Enum 4096
Name ID Label Description Type Access Class