Loading…
Name ID Label Description Type Access Class
statusinfo_0 4060 MultiEcho Trpl MultiEcho Triple - Triple reflection detected. R Enum 2050
statusinfo_1 4061 MultiEcho Dbl MultiEcho Double - Double reflection detected. R Enum 2050
statusinfo_2 4062 Tank Dim Invld Tank Dimensions Invalid - Tank dimensions exceed maximum range of the transmitter; reduce tank height and/or Sensor Offset values. R Enum 2050
statusinfo_3 4063 Info 0008 R Enum 2050
statusinfo_4 4064 Info 0010 R Enum 2050
statusinfo_5 4065 Clutter Off Hi Clutter Offset High - False target only partially captured; re-run False Target Rejection routine. R Enum 2050
statusinfo_6 4066 Scatter Target Scattered Target - Return signals scattered due to turbulence in vessel. R Enum 2050
statusinfo_7 4067 Uncertn Target Uncertain Target - Target is missing, but not determined to be lost; device is holding last valid value while confirming the target position, will continue based upon the LOE Delay value, consult Factory if problem persists. R Enum 2050
statusinfo_8 4068 DC Noise DC Noise - Excessive noise on A/D channel; consult Factory. R Enum 2050
statusinfo_9 4069 Signal Too Hi Signal Too High - Level signal amplitude is excessive; choose higher Dielectric range, reduce Turbulence or Foam settings, consult Factory if problem persists. R Enum 2050
Name ID Label Description Type Access Class