Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
diaginfo_6 | 4056 | Scatter Target | Scattered Target - Return signals scattered due to turbulence in vessel. | R | Enum | 2050 |
diaginfo_7 | 4057 | Uncertn Target | Uncertain Target - Target is missing, but not determined to be lost; device is holding last valid value while confirming the target position, will continue based upon the LOE Delay value, consult Factory if problem persists. | R | Enum | 2050 |
diaginfo_8 | 4058 | DC Noise | DC Noise - Excessive noise on A/D channel; consult Factory. | R | Enum | 2050 |
diaginfo_9 | 4059 | Signal Too Hi | Signal Too High - Level signal amplitude is excessive; choose higher Dielectric range, reduce Turbulence or Foam settings, consult Factory if problem persists. | R | Enum | 2050 |
diaginfo_10 | 405A | Signal Too Low | Signal Too Low - Level signal amplitude is insufficient; choose lower Dielectric range, increase Turbulence or Foam settings, consult Factory if problem persists. | R | Enum | 2050 |
diaginfo_11 | 405B | Info 0800 | R | Enum | 2050 | |
diaginfo_12 | 405C | IPC Bus | IPC Bus - Internal communications error; consult Factory. | R | Enum | 2050 |
diaginfo_13 | 405D | IPC Checksum | IPC Checksum - Internal communications error; consult Factory. | R | Enum | 2050 |
diaginfo_14 | 405E | IPC Length | IPC Length - Internal communications error; consult Factory. | R | Enum | 2050 |
diaginfo_15 | 405F | IPC Ack | IPC Ack - Internal communications error; consult Factory. | R | Enum | 2050 |
Name | ID | Label | Description | Type | Access | Class |