Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
Turbulence | 4025 | Turbulence | Increase choice if Quality value is consistently < 20. | R/W | Enum | 2048 |
RateChange | 4026 | Rate of Change | Select the Maximum rate of change of the level surface (rising or falling). | R/W | Enum | 2048 |
Foam | 4027 | Foam | Increase choice if Quality value is consistently < 20. | R/W | Enum | 2048 |
TankTop | 4028 | Tank Top | Select the metallic tank top structure (choose Other for non-metalic tanks). | R/W | Enum | 2048 |
TankHeight | 4029 | Tank Height | Distance from the bottom to the top of tank. | R/W | Float | 2048 |
TrimLevel | 402A | Trim Level | Trim Level is an offset value to be used to force the transmitter to output the exact Level. This should only be used after all parameters have been entered correctly, Tank Height and Sensor Offset have been confirmed accurate, and it has been confirmed that the transmitter is tracking the correct level target. | R/W | Float | 2048 |
BlockingDistance | 402B | Blocking Distance | Blocking Distance defines an area near the antenna where reflections cannot be measured effectively due to antenna ringing. It is measured from the sensor reference point (bottom of NPT thread or flange face, top of BSP thread). Level reading will never be higher than level corresponding to Blocking Distance value. Do not allow liquid onto the antenna. | R/W | Float | 2048 |
Initials | 402C | Date/Time/Initials | When and by whom calibration was performed. | R/W | PackedAscii | 2052 |
EnteredPassword | 402D | Enter Password | Password is required for adjusting Factory Settings. | W | Unsigned | 2052 |
user_password | 402E | New User Password | User password required to change parameter settings from keypad. | R/W | Unsigned | 2048 |
Name | ID | Label | Description | Type | Access | Class |