Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
MagnetrolSSN | 403B | Magnetrol S/N | Magnetrol S/N - Serial number of this unit. | R/W | ASCII | 2052 |
Initials | 403C | Date/Time/Initials | When and by whom calibration was performed. | R/W | PackedAscii | 2052 |
FirmwareVersion | 403D | Firmware Version | Field Device Software Revision- This revision corresponds to the software or firmware, that is embedded in the Field Device | R | ASCII | 2052 |
blocking_dist | 403E | Blocking Distance | Distance below the transducer face within which level is not sensed. Operation when the liquid level is within the blocking distance is undefined. | R/W | Float | 2048 |
ref_dist | 403F | Reference Distance | The reference distance is distance from the face of the transducer to the point of zero flow in the flow element. | R/W | Float | 2048 |
max_flow | 4040 | Maximum Flow | Maximum flow is the largest value that will be displayed for flow. It is calculated from the Maximum Head. | R | Float | 2050 |
max_head | 4041 | Maximum Head | Maximum head is the ohighest level allowed for the selected flow element. This value depends on which flow element is selected, and where the Model 355 is mounted. | R/W | Float | 2048 |
low_flow_cutoff | 1F51 | Low Flow Cutoff | Low flow cutoff will force a zero flow value when the level is below this point. | R/W | Float | 2048 |
custom_unit_text | 4042 | Custom Unit Text | Text describing the units for the custom unit output. | R/W | ASCII | 2048 |
custom_unit_text_fake | 4043 | Custom Unit Text | Text describing the units for the custom unit output. | R/W | Enum | 32 |
Name | ID | Label | Description | Type | Access | Class |