Name ID Label Description Type Access Class
bSwitch1State 40E6 DO Switch 1 State DO Switch physical state (0 - closed; 1 - open) R Enum 10
bSwitch2State 40E7 DO Switch 2 State DO Switch physical state (0 - closed; 1 - open) R Enum 10
fManualPos 4007 Manual Setpoint Manual Setpoint- Manual valve setpoint in %. Value must be between -5.0% and +160.0%. R Float 10
fManualSig 40C5 Set Valve Pos In mA Manual Signal- Manual valve setpoint in mA. R/W Float 8
cSetPosType 40BA Setpoint Type Setpoint Type- Selects how setpoint or signal is set. R/W Enum 4096
nSetIPValue 40D1 I/P Value IP Value. A value of 0 resets the device to allow the control task to set the I/P (changing modes ora reset also switches back to normal control modes). W Unsigned 4096
cUILockLevel 40ED Local UI LocalUI locking status. R/W Enum 8
cPositionLimitsProtected 40BD Allow Override Limit Allow diag. and self-tune to override limits R/W Enum 8
cTightShutoffEnabled 4073 Tight Shutoff Tight Shutoff Limit- Threshold for tight shutoff: when selected, if the input signal would position the valve below the tight shutoff value, full supply or atmosphere pressure is supplied to the actuator to close the valve with full seating force. Set the TS value between -1% and 20%, then enable the TS function. R/W Enum 8
fTightShutOff 4074 Tight Shutoff Value Tight Shutoff Limit- Threshold for tight shutoff: when selected, if the input signal would position the valve below the tight shutoff value, full supply or atmosphere pressure is supplied to the actuator to close the valve with full seating force. Value between -1% and 20% and not to include. R/W Float 8