Loading…

Variable Name: cTightShutoffEnabled

Variable ID: 0x4073

Variable Label: Tight Shutoff

Variable Help: Tight Shutoff Limit- Threshold for tight shutoff: when selected, if the input signal would position the valve below the tight shutoff value, full supply or atmosphere pressure is supplied to the actuator to close the valve with full seating force. Set the TS value between -1% and 20%, then enable the TS function.

Variable Handling: R/W

Variable Class: Correction

Variable Size: 1

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0000 Disabled
0x0001 Enabled

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
170 40F6 cmdReadSettings

Variable Write Command List

Command Number Command ID Command Name
171 40F7 cmdWriteSettings