Name ID Label Description Type Access Class
cPositionLimitsLowerEnabled 406B Pos Limit Low To enable or disable position lower limit R/W Enum 8
cPositionLimitsUpperEnabled 406D Pos Limit Upper To enable or disable position upper limit R/W Enum 8
fPositionLimitsLow 406C Limit Low Lower Position Limit- The SVi1000 allows the user to establish software limit stops. The control functions will NOT allow the valve position to be lower than the lower position limit. However this option DOES NOT PROVIDE MECHANICAL STOPS for the valve. During an electrical or an air failure the valve will go to the failsafe position without regard to the software limit stops. The manual position full closed or full open will similarly ignore limit stops. The value should be set between -10 and 50.0 included R/W Float 8
fPositionLimitsUpper 406E Limit Upper Upper Position Limit- The SVi1000 allows the user to establish software limit stops. The control functions will NOT allow the valve position to be above than the upper position limit.However this option DOES NOT PROVIDE MECHANICAL STOPS for the valve. During an electrical or an air failure the valve will go to the failsafe position without regard to the software limit stops. The manual position full closed or full open will similarly ignore limit stops. the range should be limited from 10.0 to 110.0. R/W Float 8
cPositionRateLowerLimitEnabled 4070 Rate Limit Down Position Rate Limit Down Enable R/W Enum 8
cPositionRateUpperLimitEnabled 4071 Rate Limit Up Postion Rate Limit Up Enable R/W Enum 8
fPositionRateLimits 4072 Pos. Rate Limits Position Rate Limits. The range shoud be between 0.8 and 100.10. R/W Float 8
cBumplessRequired 4067 Bumpless Transfer Bumpless Transfer- enables or disables the bumpless transfer mode. R/W Enum 8
nBumplessSpeed 4068 Transfer Time Transfer Time is approximately the number of seconds required to move the valve 100% toward the signal position. It is between 1 and 255 sec/100%. R/W Unsigned 8
cSPCharacterization 4066 Characterization Cam Configuration Flags- cam used - defines relationship between flow capacity (Cv) and percentage opening of the valve. Several cams are available: linear; =%50; =%30; quick opening coefficient of 50; custom; CamFlex=%. R/W Enum 8
Name ID Label Description Type Access Class