Variable Name: fPositionLimitsUpper
Variable ID: 0x406E
Variable Label: Limit Upper
Variable Help: Upper Position Limit- The SVi1000 allows the user to establish software limit stops. The control functions will NOT allow the valve position to be above than the upper position limit.However this option DOES NOT PROVIDE MECHANICAL STOPS for the valve. During an electrical or an air failure the valve will go to the failsafe position without regard to the software limit stops. The manual position full closed or full open will similarly ignore limit stops. the range should be limited from 10.0 to 110.0.
Variable Handling: R/W
Variable Class: Correction
Variable Size: 4
Variable DataType: Float
Variable Display Format: |en|.2f
Variable Edit Format: |en|6.2f
Variable Unit:
Variable Max: 110
Variable Min: 10
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
170 | 40F6 | cmdReadSettings |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
171 | 40F7 | cmdWriteSettings |