Name ID Label Description Type Access Class
bConfigFlags1_ProtectLimits 408D Allow Override Limit Allow diag. and self-tune to override limits R/W Enum 8
bConfigFlags1_LowerLimit 4090 Pos Limit Low To enable or disable position lower limit R/W Enum 8
bConfigFlags1_UpperLimit 4092 Pos Limit High To enable or disable position upper limit R/W Enum 8
bConfigFlags1_TightShutoff 4094 Tight Shutoff Tight Shutoff Limit- Threshold for tight shutoff: when selected, if the input signal would position the valve below the tight shutoff value, full supply or atmosphere pressure is supplied to the actuator to close the valve with full seating force. Set the TS value between -1% and 20%, then enable the TS function. R/W Enum 8
bConfigFlags1_Characterization 408A Characterization Cam Configuration Flags- cam used - defines relationship between flow capacity (Cv) and percentage opening of the valve. Several cams are available: linear; =%50; =%30; quick opening coefficient of 50; custom; CamFlex=%. R/W Enum 8
bConfigFlags2 4084 Local Buttons Button Configuration Flags- Defines lock level for SVI II AP buttons to avoid unintended modifications. R/W Enum 8
bConfigFlags3 40C6 Setpoint Mode Setup Configuration Flags- These options determine whether the controller setpoint will be in local, local only, remote or last mode on startup. R/W Enum 8
fTSLimit 4095 Tight Shutoff Value Tight Shutoff Limit- Threshold for tight shutoff: when selected, if the input signal would position the valve below the tight shutoff value, full supply or atmosphere pressure is supplied to the actuator to close the valve with full seating force. Value between -1% and 20% and not to include. R/W Float 8
fLowerPosLimits 4091 Limit Low Lower Position Limit- The SVI II AP allows the user to establish software limit stops. The control functions will NOT allow the valve position to be lower than the lower position limit. However this option DOES NOT PROVIDE MECHANICAL STOPS for the valve. During an electrical or an air failure the valve will go to the failsafe position without regard to the software limit stops. The manual position full closed or full open will similarly ignore limit stops. The value should be set between -10 and 50.0 not to include R/W Float 8
fUpperPosLimits 4093 Limit High Upper Position Limit- The SVI II AP allows the user to establish software limit stops. The control functions will NOT allow the valve position to be above than the upper position limit.However this option DOES NOT PROVIDE MECHANICAL STOPS for the valve. During an electrical or an air failure the valve will go to the failsafe position without regard to the software limit stops. The manual position full closed or full open will similarly ignore limit stops. R/W Float 8
Name ID Label Description Type Access Class