Variable Name: bConfigFlags2
Variable ID: 0x4084
Variable Label: Local Buttons
Variable Help: Button Configuration Flags- Defines lock level for SVI II AP buttons to avoid unintended modifications.
Variable Handling: R/W
Variable Class: Correction
Variable Size: 1
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0000 | All Enabled |
0x0001 | No Config/Cal |
0x0002 | No Manual |
0x0003 | Locked |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
210 | 4107 | cmdReadConfiguration |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
165 | 40EC | cmdWriteConfiguration |