Name ID Label Description Type Access Class
nManualResetBias 406D Manu. reset bias Only applies to P or PD control. It is the process controller output at a typical operating steady state. If the controller outputs range from 30 to 50 % at normal operation, the manual reset bias should be set at 40% in order to minimize steady state error. Value between 0 and 100% . R/W Unsigned 8
bLCFlags 406F Select Controller configuration: options. R/W BitEnum 8
nPCDeadBand 406E Dead zone When the difference between the setpoint and the process variable is less than the dead zone, the controller will take no action to change the output.Must be between 0 and 20%. R/W Unsigned 8
fRatioGain 406A Ratio gain In ratio control, the setpoint and process variable may be in different engineering units or on different scales. The relationship between the setpoint in process variable units and the raw setpoint is given by: SP(in PV unit)=ratio gain * SP + ratio bias. R/W Float 8
fRatioBias 406B Ratio bias In ratio control, the setpoint and process variable may be in different engineering units or on different scales. The relationship between the setpoint in process variable units and the raw setpoint is given by: SP(in PV)=ratio gain * SP + ratio bias. R/W Float 8
fSPCtrl 40DF local CTRL SP Local controller setpoint W Float 4096
fLevelMini 40D4 current level R Float 16
fLevelMaxi 4050 nbr of filling up Total number of filling tanks. R Float 16
nTimeEmpty 4051 time tank empty Time in day for low level. R Integer 16
nTimeFull 4052 time tank full Time in day for high level. R Integer 16