Loading…
Loading…
Variable Name: nManualResetBias
Variable ID: 0x406D
Variable Label: Manu. reset bias
Variable Help: Only applies to P or PD control. It is the process controller output at a typical operating steady state. If the controller outputs range from 30 to 50 % at normal operation, the manual reset bias should be set at 40% in order to minimize steady state error. Value between 0 and 100% .
Variable Handling: R/W
Variable Class: Correction
Variable Size: 2
Variable DataType: Unsigned
Variable Display Format: |en|.1f
Variable Edit Format: |en|5.1f
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
186 | 40CD | read_controller_loop_Parameter1 |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
187 | 40CE | write_controller_loop_Parameter1 |