名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |
---|---|---|---|---|---|---|
remote_seal_fill_fluid | 400D | RS填充液 | Remote Seal Fill Fluid- Fluid material in the device remote seal. | 读/写 | 枚举 | 2048 |
module_range_code | 4000 | 模块范围 | Module range- pressure range located on the side of the sensor | 读 | 枚举 | 2048 |
temperature_value | 4001 | Amp temp | Field Device Variable Value- Digital value that changes with respect to process or ambient temperature over time with no user intervention. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. | 读 | 浮点 | 10 |
temperature_units | 4018 | Amp temp unit | Field Device Variable Unit- Digital unit that the variable will be displayed with. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. | 读 | 枚举 | 8 |
upper_display_value | 401C | UDV | XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. UDV: Upper Disp Value- Available range is as below; -99999 to 99999 -9999.9 to 9999.9 -999.99 to 999.99 -99.999 to 99.999 -9.9999 to 9.9999 | 读/写 | 浮点 | 256 |
lower_display_value | 401D | LDV | XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. LDV: Lower Disp Value- Available range is as below; -99999 to 99999 -9999.9 to 9999.9 -999.99 to 999.99 -99.999 to 99.999 -9.9999 to 9.9999 | 读/写 | 浮点 | 256 |
digit_number_under_decimal_point | 401E | Digit_DP | XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. Digit_DP: Digit under Decimal Point- Available range is from 0 to 4 as below; 0 (XXXXX) 1 (XXXX.X) 2 (XXX.XX) 3 (XX.XXX) 4 (X.XXXX) | 读/写 | 无符号 | 256 |
unit_code | 401F | LCD_Unit | XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. There are 4 groups as below. All units appear in series. 1)Pressure(DISP=LIN)2)Level(DISP=LIN) 3)Flow(DISP=SQR) 4)Special(%and None) | 读/写 | 枚举 | 256 |
option | 4020 | LCD_Opt. | XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. | 读/写 | 无符号 | 256 |
Cut_Point_value | 4005 | Cut_Pt % | Cut_Pt: Low Cut Point- Dimension in % Flow at Calibrated Range, affects Analog Output and Transmitter LCD in SQR mode only. Available range is from 0% to 20% Flow. | 读/写 | 浮点 | 16 |
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |