Loading…
Name ID Label Description Type Access Class
write_protect 00A7 Write protect Write Protect Mode- Indicates whether variables can be written to the Field Device, or whether commands that cause actions, to be performed in the Field Device, can or cannot occur. Depending on the Field Device, this is a mode that is controllable by the user, either via the Field Device hardware or the HART Protocol. R Enum 2048
private_label_distributor 00A8 Distribuidor Private Label Distributor- References the company that is responsible for the distribution of this Field Device to customers R Enum 2048
final_assembly_number 00A9 Final asmbly num Número de ensamblaje final: Número que se utiliza con fines de identificación y está asociado al dispositivo de campo en general. R/W Unsigned 2048
xmtr_specific_status_0 0FB5 Status group 1 Estado específico del dispositivo de campo Byte 1: Datos que tiene el estado del dispositivo de campo información relativa a: fallos/advertencias/estado de los procesos. R BitEnum 2051
xmtr_specific_status_1 0FB6 Status group 2 Estado específico del dispositivo de campo Byte 2: Datos que tiene el estado del dispositivo de campo información relativa a: fallos/advertencias/estado de los procesos. R BitEnum 2051
burst_command_number 0FFD Burst option Opción de ráfaga: Selecciona las variables a las que se aplicarán ráfagas si el modo de ráfaga está activado. W Enum 128
burst_mode_select 0FFF Burst mode Burst Mode Select- Selects the mode for the Burst Mode functionality. If Burst is enabled the Field Device will generate HART messages on the Link without individual requests from the Host. W Enum 128
pressure_units 138D Unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. Pressure- Pressure of the process measured with respect to a reference pressure. R/W Enum 8
pressure_value 138E Pres Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention. Pressure- Pressure of the process measured with respect to a reference pressure. R Float 10
pressure_percent_range 138F PV % Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. Pressure- Pressure of the process measured with respect to a reference pressure. R Float 34
pressure_upper_range_limit 1393 USL Upper Sensor Limit Value- Defines the maximum useable value for the Upper Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. R Float 8
pressure_lower_range_limit 1394 LSL Lower Sensor Limit Value- Defines the minimum useable value for the Lower Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. R Float 8
pressure_minimum_span 1390 Min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. R Float 8
pressure_output_transfer_function 1391 Transfer function Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. Pressure- Pressure of the process measured with respect to a reference pressure. R/W Enum 32
pressure_upper_range_value 1396 URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. Pressure- Pressure of the process measured with respect to a reference pressure. R/W Float 32
pressure_lower_range_value 1397 LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. Pressure- Pressure of the process measured with respect to a reference pressure. R/W Float 32
pressure_damping_value 1398 Pres damp Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. Pressure- Pressure of the process measured with respect to a reference pressure. R/W Float 8
flange_type 139A Flange type Flange Type- Hardware, adjacent to the sensor, that physically connects the process to the sensor. Pressure- Pressure of the process measured with respect to a reference pressure. R/W Enum 2048
o_ring_material 139B O ring matl O Ring Material- Construction material of a seal that exists between the module and flange. R/W Enum 2048
meter_installation 139C Meter type Meter Installation- Defines whether there is a meter installed or not and possibly what information the meter will display. R/W Enum 256
remote_seal_type 139D RS type Remote Seal Type- Type of device that is capable of detecting and passing on the process pressure on to the module. This is only unambiguous if 1 remote seal is installed. R/W Enum 2048
module_fill_fluid 139E Fill fluid Sensor Fill Fluid- Fluid material in the module. R Enum 2048
number_of_remote_seals 139F Num remote seal Number of Remote Seals- Physical quantity of the seals for the remote seal that is installed. R/W Enum 2048
analog_output_value 1779 PV AO Analog Output Value- Value that tracks the Digital Value representation, under normal operating modes. Analog Output- Measureable physical output which changes with respect to time, without user intervention. R/W Float 66
analog_output_alarm_select 177A AO ALARM TYPE Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. Analog Output- Measureable physical output which changes with respect to time, without user intervention.There are 3 mode of AO Alarm Type as below; Overscale Underscale Hold last output R/W Enum 64
Name ID Label Description Type Access Class