Loading…
Name ID Label Description Type Access Class
remote_seal_fill_fluid 400D RS fill fluid Remote Seal Fill Fluid- Fluid material in the device remote seal. R/W Enum 2048
module_range_code 4000 Module rnge Module range- pressure range located on the side of the sensor R Enum 2048
temperature_value 4001 Amp temp Field Device Variable Value- Digital value that changes with respect to process or ambient temperature over time with no user intervention. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. R Float 10
temperature_units 4018 Amp temp unit Field Device Variable Unit- Digital unit that the variable will be displayed with. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. R Enum 8
upper_display_value 401C UDV XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. UDV: Upper Disp Value- Available range is as below; -99999 to 99999 -9999.9 to 9999.9 -999.99 to 999.99 -99.999 to 99.999 -9.9999 to 9.9999 R/W Float 256
lower_display_value 401D LDV XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. LDV: Lower Disp Value- Available range is as below; -99999 to 99999 -9999.9 to 9999.9 -999.99 to 999.99 -99.999 to 99.999 -9.9999 to 9.9999 R/W Float 256
digit_number_under_decimal_point 401E Digit_DP XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. Digit_DP: Digit under Decimal Point- Available range is from 0 to 4 as below; 0 (XXXXX) 1 (XXXX.X) 2 (XXX.XX) 3 (XX.XXX) 4 (X.XXXX) R/W Unsigned 256
unit_code 401F LCD_Unit XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. There are 4 groups as below. All units appear in series. 1)Pressure(DISP=LIN)2)Level(DISP=LIN) 3)Flow(DISP=SQR) 4)Special(%and None) R/W Enum 256
option 4020 LCD_Opt. XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. R/W Unsigned 256
Cut_Point_value 4005 Cut_Pt % Cut_Pt: Low Cut Point- Dimension in % Flow at Calibrated Range, affects Analog Output and Transmitter LCD in SQR mode only. Available range is from 0% to 20% Flow. R/W Float 16
Cut_Mode_value 4006 Cut_Mode Cut_Mode: Low Cut Mode- Output mode below Low Cut Point, affects Analog Output and Transmitter LCD in SQR mode only. Available mode is LINEAR or ZERO. R/W Enum 16
burnout_current_overscale 4027 Overscale Overscale_Current is able to set in the range from 20.8mA to 21.6mA. R/W Enum 16
burnout_current_underscale 4028 Underscale Underscale_Current is able to set in the range from 3.2mA to 3.8mA. R/W Enum 16
cell_body_no 400C Cell B/N Cell B/N: Cell_Body_No- Manufacturer Cell Body Number consist of 8 digits(max.), read only. R PackedAscii 2048
model_code 4014 Model_Code Model Code- Manufacturer Model Code consist of 16 digits(max.) not including hyphen. R/W PackedAscii 2048
serial_number 4015 Ser-No Ser-No: Serial_Number- Manufacturer Serial Number consist of 8 digits(max.), read only. R PackedAscii 2048
unique_device_type_code 07ED R/W Enum 128
rosemount_model_code 07F5 R/W Enum 2048
rosemount_analytical_model_code 07F6 R/W Enum 2048
kayray_model_code 07F7 R/W Enum 2048
micro_motion_model_code 07F8 R/W Enum 2048
units_code 07E9 R/W Enum 4096
transfer_function_code 07EA R/W Enum 4096
material_code 07EC R/W Enum 4096
alarm_selection_code 07EB R/W Enum 4096
write_protect_code 07EE R/W Enum 2048
company_identification_code 07EF R/W Enum 128
burst_mode_control_code 07F0 R/W Enum 128
physical_signaling_codes 07F1 R/W Enum 2048
flag_assignment 07F2 R/W Enum 128
operating_mode_code 07F3 R/W Enum 2048
analog_output_numbers_code 07F4 R/W Enum 4096
response_code 0096 Command Specific Response Code- Data that is returned in the Field Device response, that indicates the relative success of the Command sent in the Host request. This information may relate to the Data of the Host request or to the command itself. R/W Enum 129
comm_status 0098 Communications Error Summary- The Field Device has detected the following error condition while attempting to receive the Host request. Therefore the Command was not accepted, and the Host request caused no change to occur in the Field Device. R/W BitEnum 131
device_status 0097 Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process R/W BitEnum 131
manufacturer_id 0099 Manufacturer Manufacturer Identification Code- References a specific manufacturer, which is usually a company name, that is responsible for the manufacture of this Field Device. R Enum 128
device_type 009A Model Model- References the type of Field Device, usually an advertised model number, that is unique to a single manufacturer R Enum 128
request_preambles 009B Num req preams Number of Request Preambles- Number of Preambles required from the Host request by the Field Device R Unsigned 128
universal_revision 009C Universal rev Universal Revision- Revision of the Universal Device Description, that the Field Device conforms to R Unsigned 128
transmitter_revision 009D Fld dev rev Field Device Revision- Revision of the Field Device Specific Device Description, that the Field Device conforms to R Unsigned 128
software_revision 009E Software rev Field Device Software Revision- This revision corresponds to the software or firmware, that is embedded in the Field Device R Unsigned 2048
hardware_revision 009F Hardware rev Hardware Revision- Revision that corresponds to the electronics hardware of the Field Device. R Unsigned 2048
physical_signaling_code 00AB Physicl signl code Physical Signaling Code- The Physical Signaling Code describes the type of Physical Layer that has been implemented in the hardware that is responsible for the HART Communication port R Enum 2048
device_flags 00A0 Dev flags Field Device Flags- Describes special features of the Field Device that affect the Data Link Layer R BitEnum 128
device_id 00A1 Dev id Field Device Identification- Uniquely identifies the Field Device when combined with the Manufacturer Identification and Device Type. Therefore, this variable cannot be modified by the Host user. R Unsigned 128
polling_address 00A2 Poll addr Polling Address- Address used by the Host to identify a Field Device, and changeable by the User to control: the Multidrop Mode for Analog Output 1), and the Analog Output Fixed Mode of Analog Output 1) W Unsigned 128
tag 00A3 Tag Tag- Text that is associated with the Field Device installation. This text can be used by the user in any way. A recommended use is as a unique label to a plant that correlates to a Field Device label: a plant drawing, or on a Control System. This variable is also used as a type of data link layer address handle. R/W PackedAscii 2048
message 00A4 Message Message- Text that is associated with the Field Device. This text can be used by the user in any way. There is no recommended use. R/W PackedAscii 2048
descriptor 00A5 Descriptor Descriptor- Text that is associated with the Field Device. This text can be used by the user in any way. There is no specific recommended use. R/W PackedAscii 2048
date 00A6 Date Date- Gregorian calendar date that is stored in the Field Device. This date can be used by the user in any way. There is no specific recommended use. R/W HartDate 2048
Name ID Label Description Type Access Class