Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
remote_seal_fill_fluid | 400D | RS fill fluid | Remote Seal Fill Fluid- Fluid material in the device remote seal. | R/W | Enum | 2048 |
module_range_code | 4000 | Module rnge | Module range- pressure range located on the side of the sensor | R | Enum | 2048 |
temperature_value | 4001 | Amp temp | Field Device Variable Value- Digital value that changes with respect to process or ambient temperature over time with no user intervention. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. | R | Float | 10 |
temperature_units | 4018 | Amp temp unit | Field Device Variable Unit- Digital unit that the variable will be displayed with. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. | R | Enum | 8 |
upper_display_value | 401C | UDV | XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. UDV: Upper Disp Value- Available range is as below; -99999 to 99999 -9999.9 to 9999.9 -999.99 to 999.99 -99.999 to 99.999 -9.9999 to 9.9999 | R/W | Float | 256 |
lower_display_value | 401D | LDV | XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. LDV: Lower Disp Value- Available range is as below; -99999 to 99999 -9999.9 to 9999.9 -999.99 to 999.99 -99.999 to 99.999 -9.9999 to 9.9999 | R/W | Float | 256 |
digit_number_under_decimal_point | 401E | Digit_DP | XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. Digit_DP: Digit under Decimal Point- Available range is from 0 to 4 as below; 0 (XXXXX) 1 (XXXX.X) 2 (XXX.XX) 3 (XX.XXX) 4 (X.XXXX) | R/W | Unsigned | 256 |
unit_code | 401F | LCD_Unit | XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. There are 4 groups as below. All units appear in series. 1)Pressure(DISP=LIN)2)Level(DISP=LIN) 3)Flow(DISP=SQR) 4)Special(%and None) | R/W | Enum | 256 |
option | 4020 | LCD_Opt. | XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. | R/W | Unsigned | 256 |
Cut_Point_value | 4005 | Cut_Pt % | Cut_Pt: Low Cut Point- Dimension in % Flow at Calibrated Range, affects Analog Output and Transmitter LCD in SQR mode only. Available range is from 0% to 20% Flow. | R/W | Float | 16 |
Cut_Mode_value | 4006 | Cut_Mode | Cut_Mode: Low Cut Mode- Output mode below Low Cut Point, affects Analog Output and Transmitter LCD in SQR mode only. Available mode is LINEAR or ZERO. | R/W | Enum | 16 |
burnout_current_overscale | 4027 | Overscale | Overscale_Current is able to set in the range from 20.8mA to 21.6mA. | R/W | Enum | 16 |
burnout_current_underscale | 4028 | Underscale | Underscale_Current is able to set in the range from 3.2mA to 3.8mA. | R/W | Enum | 16 |
cell_body_no | 400C | Cell B/N | Cell B/N: Cell_Body_No- Manufacturer Cell Body Number consist of 8 digits(max.), read only. | R | PackedAscii | 2048 |
model_code | 4014 | Model_Code | Model Code- Manufacturer Model Code consist of 16 digits(max.) not including hyphen. | R/W | PackedAscii | 2048 |
serial_number | 4015 | Ser-No | Ser-No: Serial_Number- Manufacturer Serial Number consist of 8 digits(max.), read only. | R | PackedAscii | 2048 |
unique_device_type_code | 07ED | R/W | Enum | 128 | ||
rosemount_model_code | 07F5 | R/W | Enum | 2048 | ||
rosemount_analytical_model_code | 07F6 | R/W | Enum | 2048 | ||
kayray_model_code | 07F7 | R/W | Enum | 2048 | ||
micro_motion_model_code | 07F8 | R/W | Enum | 2048 | ||
units_code | 07E9 | R/W | Enum | 4096 | ||
transfer_function_code | 07EA | R/W | Enum | 4096 | ||
material_code | 07EC | R/W | Enum | 4096 | ||
alarm_selection_code | 07EB | R/W | Enum | 4096 | ||
Name | ID | Label | Description | Type | Access | Class |