Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
output_analog_value | 4008 | Output I | Refers to the actual valve position in terms of current in mA. | R | Float | 66 |
damping_val | 4009 | PV Damp | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R | Float | 8 |
input_upper_value | 400A | FS In | Refers to the input current to move the valve to full open / close position in normal / reverse operation. | R | Float | 32 |
input_lower_value | 400B | Zero In | Refers to the input current to move the valve to full open / close position in normal / reverse operation. | R | Float | 32 |
output_upper_value | 400C | FS Out | Refers to the output current when the valve is at full open / close position in normal / reverse operation. | R | Float | 32 |
output_lower_value | 400D | Zero Out | Refers to the output current when the valve is at full open / close position in normal / reverse operation. | R | Float | 32 |
sensor_serial_number | 400E | Sensor Serial | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R | Unsigned | 32 |
min_sensor_span | 400F | Min_Sensor_Span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. | R | Float | 32 |
flow_type | 4014 | Flow Type | The positioner supports Linear, Quick Opening, and Equal Percentage flow types. | R/W | Enum | 32 |
reserved_1 | 4015 | R/W | Integer | 1025 | ||
Name | ID | Label | Description | Type | Access | Class |