Name ID Label Description Type Access Class
setpoint_value 4000 Setpoint Refers to the requested position in terms of percent. R Float 10
position_value 4001 Position Refers to the actual valve position in terms of percent. R Float 10
pressure_value 138E Pressure Refers to the output pressure of OUT 1 of the positioner in terms of percent. R Float 10
setpoint_units 4002 Setpoint Units Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R/W Enum 8
position_units 4003 Position Units Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R Enum 8
pressure_units 138D Pressure Units Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R Enum 8
sensor_units 4004 Sensor Units Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R Enum 8
range_units 4005 PV rnge unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R Enum 8
analog_alarm_code 4006 AO Alrm typ Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. R Enum 64
input_analog_value 4007 Input I Refers to the requested position in terms of current in mA. R Float 66