Name ID Label Description Type Access Class
cell_temp 4000 Snsr temp Temperatura del sensor: Temperatura del sensor que está haciendo la medición del proceso R Float 10
cell_temp_units 4001 R Enum 8
secondary_output 400F SOut Secondary Output (SOut) - User scaled output which tracks the transmitter % of range. The Secondary Output displays in user defined engineering units (6 ASCII characters) with the output value based on the PV percent of range as applied to the Secondary Output lower and upper range values. R Float 34
secondary_units 4010 SO Units Secondary Output (SO) Units - User defined units for the Secondary Output (6 ASCII characters) R/W ASCII 32
sec_lower_range 4012 SOut LRV Secondary Output (SOut) Lower Range Value - Defines the operational endpoint from which the Secondary Output 0% point is derived. R/W Float 32
sec_upper_range 4013 SOut URV Secondary Output (SOut) Upper Range Value - Defines the operational endpoint from which the Secondary Output 100% point is derived. R/W Float 32
lo_temp_alarm_sp 4016 Lo Temp Alarm SP Low Temperature Alarm Set Point - Temperature setting at which the transmitter will generate an alarm status (Cell Temp Under) if the pressure sensor (cell) temperature is equal to or less than this value. R/W Float 9
hi_temp_alarm_sp 4017 Hi Temp Alarm SP High Temperature Alarm Set Point - Temperature setting at which the transmitter will generate an alarm status (Cell Temp Over) if the pressure sensor (cell) temperature is equal to or greater than this value. R/W Float 9
dummy 401A R Unsigned 64
fail_mode 401B Fail Mode Fail Mode - Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. R/W Enum 64