Name ID Label Description Type Access Class
temperature_comp_ch01 4017 Temperature Compensation Sets temperature compensation on or off. R Enum 2048
loss_time_ch01 401A LossTime This is amount of time between last receiving a correct echo and going into the Fail-safe condition. This time period is timed in seconds. This cannot be reduced to less than 30 seconds. R/W Unsigned 2048
fail_safe_ch01 401D If a loss of echo condition is reached, then the 4-20mA output will follow the configured settings: 3.60mA, 4mA, 20mA, 21mA, or Hold the reading at the last recognized echo. This is usually due to a cable being cut or the instrument not being set up correctly. R/W Enum 2048
activate_linearizer_ch01 4020 Activate Linearizer Activate the Linerarizer. R/W Enum 2048
sw_revision_str 4023 Software Build R ASCII 2048
password_int 4024 password int W Unsigned 2048
password_ascii 4025 Access to Configuration Menus R/W Password 4096
goodpassword 4027 R/W Enum 4096
new_password_int 402A password int W Unsigned 2048
relay_01_going_to_counter 4038 R/W Enum 4096