Variable Name: fail_safe_ch01
Variable ID: 0x401D
Variable Label:
Variable Help: If a loss of echo condition is reached, then the 4-20mA output will follow the configured settings: 3.60mA, 4mA, 20mA, 21mA, or Hold the reading at the last recognized echo. This is usually due to a cable being cut or the instrument not being set up correctly.
Variable Handling: R/W
Variable Class: Device
Variable Size: 1
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0000 | 3.6 ma |
0x0001 | 4 ma |
0x0002 | Hold |
0x0003 | 20 ma |
0x0004 | 21 ma |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
None
Variable Write Command List
None