Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label:

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R/W

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 Analog output 1 and its digital representation are outside the operating range limits, and not responding to input
0x0008 Analog output 1 and its digital representation are in fixed mode, and not responsive to input changes
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
150 4029 read_low_cut_info
153 402C read_bi_dir_mode
155 402E read_disp_mode
157 4030 read_engr_disp_range
159 4032 read_engr_disp_value
160 4033 read_module_tp_rng
161 4034 read_eja_data_material
163 4036 read_sensor_trim_point
164 4037 read_ext_sw_mode
166 4039 read_model
167 403A read_tmp_sp_unit
169 403C read_serial_no
176 403D read_h2o_unit_select
180 404E read_si_option
182 405E read_amp_temp
183 405F read_auto_recover
248 4050 read_joker_password_log
249 4051 read_passwords_for_wrt_protect
170 4062 read_ao_range
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
12 00B4 read_message
13 00B5 read_tag_descriptor_date
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
16 00B8 read_final_assembly_number
48 0FCE read_additional_transmitter_status

Variable Write Command List

None