Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label: Device status

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 PV Analog Channel Saturated
0x0008 PV Analog Channel Fixed
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
128 4268 read_factory_options
130 426A read_basic_configuration
132 426C read_hysteresis_configuration
134 426E read_PST_configuration
136 4270 read_cycle_counts
142 4275 read_last_cal_info
150 4277 get_integrator_signature_info_data
151 4278 get_installer_signature_info_data
152 4279 get_baseline_signature_info_data
153 427A get_selected_maintenance_signature_info_data
154 427B get_basic_signature_info_data1
155 427C get_basic_signature_info_data2

Variable Write Command List

None