Loading…

Variable Name: pst_breakaway_trend_low_limit

Variable ID: 0x4030

Variable Label: PST Breakaway Pressure Low Limit

Variable Help: Low limit for partial stroke test breakaway pressure: For single-acting: 1.5 bar. For double-acting: 0.05 bar.

Variable Handling: R/W

Variable Class: Diagnostic | Device

Variable Size: 4

Variable DataType: Float

Variable Display Format: |en|5.1f

Variable Edit Format: |en|5.1f

Variable Unit:

Variable Max:

Variable Min:

Variable Read Command List

Command Number Command ID Command Name
162 4696 read_lifecycle_diagnostics_limits

Variable Write Command List

Command Number Command ID Command Name
131 4589 write_float_parameter