Variable Name: auto_pst_interval

Variable ID: 0x402D

Variable Label: Automated PST Interval

Variable Help: The period between automated tests. Set test interval according to process application Safety Integrity Level (SIL) targets and used valve assembly. Recommended value (default) = 720 hours (30 days)

Variable Handling: R/W

Variable Class: Device

Variable Size: 4

Variable DataType: Float

Variable Display Format: |en|6.2f

Variable Edit Format: |en|8.2f

Variable Unit:

Variable Max: 8760

Variable Min: 0.017

Variable Read Command List

Command Number Command ID Command Name
136 45A0 read_partial_stroke_test_parameters

Variable Write Command List

Command Number Command ID Command Name
131 4589 write_float_parameter