Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label: Device status

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 PV Analog Channel Saturated
0x0008 PV Analog Channel Fixed
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
242 4001 read_mii_model_type
208 4281 read_rangealarm
180 42D3 read_customcurve_info
180 42D3 read_customcurve_info
180 42D3 read_customcurve_info
180 42D3 read_customcurve_info
182 42D5 read_customcurve_point
182 42D5 read_customcurve_point
182 42D5 read_customcurve_point
182 42D5 read_customcurve_point

Variable Write Command List

None