Loading…

Variable Name: KDGM_curve_profile

Variable ID: 0x402E

Variable Label: Non-Linear Profile P011

Variable Help: Non-Linear Profile - select a non-linear profile for the appropriate Flow or Contents application. This will automatically set up the required parameters such as P013, P014 and P030 to P039. A selection of SPECIAL allows individual point values to be changed.

Variable Handling: R/W

Variable Class: InputBlock

Variable Size: 1

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0001 Linear
0x0002 Special Plotted
0x0003 Horizontal Cylinder Flat
0x0004 Spherical
0x0006 Horizontal Cylinder Domed
0x0007 Flume/weir (3/2)
0x0008 V-notch (5/2)
0x000E Manning
0x0029 Parshall 1 in
0x002A Parshall 2 in
0x002B Parshall 3 in
0x002E Parshall 6 in
0x0031 Parshall 9 in
0x0033 Parshall 1 ft
0x003D Parshall 1.5 ft
0x0034 Parshall 2 ft
0x0035 Parshall 3 ft
0x0036 Parshall 4 ft
0x0037 Parshall 5 ft
0x0038 Parshall 6 ft
0x003A Parshall 8 ft
0x003C Parshall 10 ft
0x0064 Special Calculated

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
149 4098 KDGM_read_output_data

Variable Write Command List

Command Number Command ID Command Name
151 409A KDGM_write_curve_profile