Variable Name: maximum_retries
Variable ID: 0x4047
Variable Label: Maximum Retries
Variable Help: Maximum Retries - P257: If a desludge sequence is initiated but the Stop condition does not occur before the maximum time allowed has elapsed then the system will retry after the Minimum Off Time has elapsed. If the system retries more times than the Maximum Retries value then an Alarm condition may be signalled. This parameter and associated timing parameters are only editable locally on the Control Unit.
Variable Handling: R/W
Variable Class: Device
Variable Size: 1
Variable DataType: Unsigned
Variable Display Format: |en|3u
Variable Edit Format: |en|3u
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
166 | 408C | read_custom_setup |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
169 | 4097 | write_custom_maximum_retries |