Variable Name: dig_comm_fault_code

Variable ID: 0x40DE

Variable Label: Digital Communications Fault Action

Variable Help: This fault setting applies to Modbus on RS485 and the display. Downscale: Hold process variables at values that are less than the Lower Sensor Limits and stop totalizing. Upscale: Hold process variables at values that are greater than the Upper Sensor Limits and stop totalizing. Not-a-Number: Set all process variables to IEEE NaN. IntZero-All 0: Set all process variables to 0. IntZero-Flow 0: Set flow rate to 0. None: Process variables displayed as measured (NOTE: Use alternative method to detect fault conditions when NONE is selected)

Variable Handling: R/W

Variable Class: Service | Correction

Variable Size: 1

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0000 Upscale
0x0001 Downscale
0x0002 Internal Zero - All 0
0x0003 Not-a-Number
0x0004 Internal Zero - Flow 0
0x0005 None

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

None

Variable Write Command List

None