Loading…

Variable Name: install_factor_A

Variable ID: 0x4021

Variable Label: A

Variable Help: Install Factors - A, B, C; Install Factors are utilized in situations when the measured flow rate may need to be adjusted due to variations in flow profile or other installation factors. The Install Factors are the coefficients of the polynomial equation: Corrected Flow = A + Bv + Cv^2 where v is the velocity measured by the TA2.

Variable Handling: R/W

Variable Class: InputBlock

Variable Size: 4

Variable DataType: Float

Variable Display Format: |en|.6f

Variable Edit Format: |en|.6f

Variable Unit:

Variable Max:

Variable Min:

Variable Read Command List

Command Number Command ID Command Name
153 4060 read_install_factor_A

Variable Write Command List

Command Number Command ID Command Name
154 4061 write_install_factor_A