Loading…
Loading…
Variable Name: Turbulence
Variable ID: 0x470E
Variable Label: Turbulencia
Variable Help: Un parametron que afecta la ganancia y promedios. Ajuste tipico = Medio. Incremente este parametro si la lectura de nivel es inestable y/o si el valor de la Intensidad del Eco es <20.
Variable Handling: R/W
Variable Class:
Variable Size: 1
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0000 | Ninguno |
0x0001 | Ligero |
0x0002 | Medio |
0x0003 | Pesado |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
189 | 4A0D | read_Turbulence_RateChange_Foam |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
190 | 4A0E | set_Turbulence_RateChange_Foam |