Variable Name: TargetAlgorithm
Variable ID: 0x4712
Variable Label: Target Selection
Variable Help: First will allow the detection of first valid target(first echo above threshold). First is default and is used in majority of applications. In some cases, Echo Rejection will need to be run to ensure Level appears as the first valid target. Largest will allow the detection of the largest target. Contact Technical Support before using. First Moving Echo (FME) will allow the detection of first valid moving target above the threshold. FME can be used where mixing blades create problematic false echoes.
Variable Handling: R/W
Variable Class:
Variable Size: 1
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0000 | First Echo |
0x0001 | Largest Echo |
0x0002 | First Moving Echo |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
153 | 49EC | read_Threshold_modes |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
154 | 49ED | set_Threshold_modes |