Loading…
Loading…
Variable Name: TargetThreshMode
Variable ID: 0x4713
Variable Label: Target Thresh Mode
Variable Help: Automatic Threshold is used to detect the strongest Echo and should be used when it is ensured that only one medium is present. Generally use Automatic Threshold with Target Selection set to First Echo. Fixed Threshold is used to detect the first, valid Echo and should be used in cases where stratification can occur. For example, applications of hydrocarbon over water bottoms.
Variable Handling: R/W
Variable Class:
Variable Size: 1
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0000 | Automatic |
0x0001 | Fixed Value |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
153 | 49EC | read_Threshold_modes |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
154 | 49ED | set_Threshold_modes |