Variable Name: velTrMax
Variable ID: 0x4118
Variable Label: Tracing velocity
Variable Help: To avoid faulty measurements, the BM 70 A/P /700/702 places a symmetrical "plausibility range" around the last valid measured value in which the next measured value is expected. Measured values outside this range are identified as invalid and are suppressed. If no valid measured value is identified, the BM 70 A/P /700/702 enlarges the plausibility range with the tracing speed until a valid (plausible) measured value has again been found. The measured value for level/distance cannot change at a faster rate than the set tracing speed. · Under this function the maximum rate at which the level can change in the tank should be set as the minimum value. · Setting ranges: BM 70 A/700/702: 0.01 - 10.00 m/min (0.03 - 32.80 ft/min) BM 70 P: 0.01 - 1.00 m/min (0.03 - 3.28 ft/min) · Default: 0.5 m/min (BM 70 A/700); 0.1 m/min (BM 70 P) · See also Sect. 8.8 of 'Operating Manual' (error message: NO M.VALUE) (Fct. 3.5.4)
Variable Handling: R/W
Variable Class: Correction
Variable Size: 4
Variable DataType: Float
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max:
Variable Min: 0.01
Variable Read Command List
None
Variable Write Command List
None