Variable Name: nozzle_length
Variable ID: 0x401C
Variable Label: Nozzle Length
Variable Help: Also known as nozzle blanking distance, this setting allows the transmitter to ignore anything within the designated distance. The distance will be in the units designated in the UNITS parameter. At a minimum, enter the length of the mounting nozzle from the face of the sensor to the ceiling of the tank. Additional distance can be added in order to ignore unwanted false reflections. 2CAUTION: This entry will allow the transmitter to ignore any reading in the designated area including the level you are measuring if it rises to this range. 2WARNING - Adjustment of this parameter may disturb settings in your Extended Parameters. Please verify Extended Parameters are set correctly for the application
Variable Handling: R/W
Variable Class: Device
Variable Size: 4
Variable DataType: Float
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max:
Variable Min:
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
151 | 4075 | read_basic_device_setup |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
154 | 4078 | write_probe_nozzle_length |