Loading…
Loading…
变量名称: measure_mode
变量ID: 0x402E
变量标签: Measure Mode
变量描述: The MT5xxx can be used to measure Media Level or Ullage. Media Level refers to a Level Measurement from the end of the probe to the surface of the product level. Said differently, it is measuring the amount of product in the tank. 2Ullage refers to a Level Measurement from the face of the sensor to the surface of the product being measured. Said differently, it is measuring the amount of vapor space in the tank. 2Factory default the MEASURE MODE will be Media Level. Media Level = Level in the tank Ullage = vapor space in the tank
变量处理: 读/写
变量分类: 设备
变量长度: 1
变量数据类型: 枚举
变量枚举值 | 变量枚举文本 |
---|---|
0x0000 | Media Level |
0x0001 | Ullage |
变量显示格式:
变量编辑格式:
变量单位:
变量最大值: N/A
变量最小值: N/A
变量读取命令列表
命令号 | 命令ID | 命令名称 |
---|---|---|
151 | 4075 | read_basic_device_setup |
160 | 407B | read_extended_setup |
变量写入命令列表
无