Variable Name: loop_control_choice
Variable ID: 0x4002
Variable Label: Loop Control Mode
Variable Help: Select the loop control mode: 1.Averaging: The loop control method will be (Sensor+Sensor2)/2. 2.Differential: The loop control method will be (Sensor-Sensor2). 3.Sensor: The loop current will be dependent on Sensor solely. 4.Sensor2: The loop current will be dependent on Sensor2 solely. 5.Redundant: If Sensor input fails, loop current is controlled by Sensor2 input. 6.Split Ranging: The range of both sensors will be split into 2 ranges. Range 1 will be controlled by Sensor and Range 2 will be controlled by Sensor2.
Variable Handling: R/W
Variable Class: Dynamic | Correction
Variable Size: 1
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0000 | Average |
0x0001 | Differential |
0x0002 | Sensor |
0x0003 | Sensor2 |
0x0004 | Redundant |
0x0005 | Split Range |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
188 | 4181 | read_loop_hysterisis_dampval |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
189 | 4182 | write_loop_control_variable |