Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label: Device status

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 Analog output 1 and its digital representation are outside the operating range limits, and not responding to input
0x0008 Analog output 1 and its digital representation are in fixed mode, and not responsive to input changes
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
142 4177 read_cable_resistance
146 4179 read_current_output_range_values
148 417B read_device_serial_number
150 417C read_sensor_error_values
155 4180 read_diff_measure_max
157 4182 read_reset_device_variable_min_max
1024 4183 read_temperature_status
1025 4184 read_temperature_config
1026 4185 read_thermocoupler_config
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
9 00DD read_device_variables_and_status
7 00DB read_loop_configuration
8 00DC read_dynamic_variable_classification
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
12 00B4 read_message
13 00B5 read_tag_descriptor_date
16 00B8 read_final_assembly_number
20 00DE read_long_tag
48 1043 read_additional_device_status
48 1043 read_additional_device_status
33 1054 read_device_variables
50 1052 read_device_variable_assignments
54 1057 read_device_variable_information
76 1045 read_lock_device_state
80 1046 read_device_variable_trim_point
81 104A read_device_variable_trim_guidelines
90 115E read_real_time_clock
91 11D2 read_trend_configuration
93 11D4 read_trend
95 11DD read_device_communication_statistics
105 1063 read_burst_mode_configuration

Variable Write Command List

None