Loading…
Loading…
Variable Name: sensor1_id
Variable ID: 0x40C2
Variable Label: Sensor Id
Variable Help: Sensor Id is a Read only parameter and in Online,this parameter will Read from the device as per user configured.For offline,this selection is must because of dependency for other parameters.So, select sensor 1 Id as per sensor 1 type and Id of the sensor 1 configured(Supported combinations for Sensor 1 Type and Sensor 2 Type are TC-TC,RTD-RTD).
Variable Handling: R/W
Variable Class: Correction
Variable Size: 1
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0002 | TC Type E |
0x0003 | TC Type J |
0x0004 | TC Type K |
0x0005 | TC Type N |
0x0006 | TC Type T |
0x0007 | TC Type S |
0x0008 | TC Type R |
0x0009 | TC Type B |
0x000A | RTD Pt 25 |
0x000B | RTD Pt 100 |
0x000C | RTD Pt 200 |
0x000D | RTD Pt 500 |
0x000E | RTD Pt 1000 |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
136 | 42DD | read_sensor1_configuration |
Variable Write Command List
None