Variable Name: device_status

Variable ID: 0x0097

Variable Label: Device status

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 PV Analog Channel Saturated
0x0008 PV Analog Channel Fixed
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
167 4029 get_PV_Mode
170 402C get_AO
158 404B read_warn_relay_latched
160 404D read_warn_relay_DeEN
162 404F read_alarm_relay_latched
164 4051 read_alarm_relay_DeEN
166 4053 read_sensitivity
150 4055 read_clock
152 4057 read_run_time_seconds
168 407A read_error_status
128 407B read_dip_switch_override
130 407D read_dip_sw_settings
131 407F read_unit_options
133 4082 read_COPM_fault
156 4086 read_remote_alarm_test
137 4087 read_unit_temperature
169 4088 read_line_voltage
139 408A read_TL104_test_mode
140 408B read_alarm_delay
142 4090 read_TL104_timestamp
143 4091 read_logging_event_counter
145 4094 read_Wlogging_event_number
155 4096 read_event_index
146 4098 read_Alogging_event_number
147 409A read_Flogging_event_number
148 409C read_Mlogging_event_number
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
9 00DD read_device_variables_and_status
7 00DB read_loop_configuration
8 00DC read_dynamic_variable_classification
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
12 00B4 read_message
13 00B5 read_tag_descriptor_date
16 00B8 read_final_assembly_number
20 00DE read_long_tag
48 1043 read_additional_device_status

Variable Write Command List