Loading…

Variable Name: nPosComp

Variable ID: 0x4054

Variable Label: Position Comp.

Variable Help: The response of the valve is different when the valve is nearly closed than when nearly open. This coefficient allows the user to make adjustments to try to equalize the valve response. Normal value is 6 and this value is ranging from 2 to 20.

Variable Handling: R/W

Variable Class: Correction

Variable Size: 2

Variable DataType: Unsigned

Variable Display Format: |en|2d

Variable Edit Format: |en|2d

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
216 411E cmdReadPidData

Variable Write Command List

Command Number Command ID Command Name
173 40FD cmdWritePidData