Loading…
Loading…
Variable Name: bFaultCode4
Variable ID: 0x409E
Variable Label: Fault Code 4
Variable Help: Reports Device Errors
Variable Handling: R
Variable Class: Dynamic | Diagnostic
Variable Size: 1
Variable DataType: BitEnum
Variable Enum Value | Variable Enum Text |
---|---|
0x0001 | Ref Voltage Failure |
0x0002 | Position Sensor Failure |
0x0004 | Current Sensor Failure |
0x0008 | Temperature Sensor Failure |
0x0010 | Reserved |
0x0020 | Pressure 1 Fault |
0x0040 | Pressure 2 Fault |
0x0080 | Pressure 3 Fault |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
136 | 41EF | cmdReadFaults |
Variable Write Command List
None